Earthing Strip

Earthing Strip

earthing strip images

We manufacture Earthing Strips as per IS: 2062 / 2629 / 4759. All our products comply IS: 3043 (Standard Code of Earthing Practices). Our product ranges from 20 mm x 3 mm to 125 x 16 mm. We guarantee a average minimum galvanization thickness of 86 microns to our clients. However we can also provide higher galvanization thickness such as 100 microns, 150 microns etc. depending on the requirement of clients. We source our raw materials from reputed re-rollers only. We keep sufficient stock of Industry standard sizes such as

earthing strip manufacturer

Earthing Pipe:

We manufacture both Galvanized as well as cast Iron Earthing Pipes designed as per IS: 3043 (Standard Code of Earthing Practices). We use raw materials complying to IS: 1239 (part – I) sourced from reputed sources such as Nezone, Jindal, Bansal, etc. Our products come in a minimum 40 mm dia and goes upto 100 mm dia. For Earthing in soft soils, our products come in standard 3000 mm length and for rocky soils minimum 6000 mm length but can be can customized for both nature of soils as per client’s requirements.

earthing strip images

Cable Tray Accessories:

We manufacture various kinds of accessories for cable trays such as:

All bends, tees can be customized as per the client requirements.

We manufacture Earthing Strips as per IS: 2062 / 2629 / 4759. All our products comply IS: 3043 (Standard Code of Earthing Practices). Our product ranges from 20 mm x 3 mm to 125 x 16 mm. We guarantee an average minimum galvanization thickness of 86 microns to our clients. However we can also provide higher galvanization thickness such as 100 microns, 150 microns etc. depending on the requirement of clients. We source our raw materials from reputed re-rollers only.

We keep sufficient stock of Industry standard sizes such as

The GI Earthing Conductor sizes for various Equipment:

NoEquipmentsEarth Strip Size
1HT switchgear, structures, cable trays & fence, rails, gate and steel column50 X 6 mm (GI)
2Lighting Arrestor25 X 3 mm (Copper)
3PLC Panel25 X 3 mm (Copper)
4DG & Transformer Neutral50X6 mm (Copper)
5Transformer Body50X6 mm (GI)
6Control & Relay Panel25 X 6 mm (GI)
7Lighting Panel & Local Panel25 X 6 mm (GI)
8Distribution Board25 X 6 mm (GI)
9Motor up to 5.5 kw4 mm2 (GI)
10Motor 5.5 kw to 55 kw25 X 6 mm (GI)
11Motor 22 kw to 55 kw40 X 6 mm (GI)
12Motor Above 55 kw75 X 6 mm (GI)

Selection of Earthing System:

Installations/       ISC CapacityIR Value RequiredSoil Type/ ResistivityEarth System
Household earthing/3kA8 ohmNormal Soil/ up to 50 ohm-meterSingle Electrode
Sandy Soil/ between 50 to 2000 ohm- meterSingle Electrode
Rocky Soil/ More than 2000 ohm- meterMultiple Electrodes
Commercial premises, Office / 5kA2 ohmNormal Soil/ up to 50 ohm-meterSingle Electrode
Sandy Soil/ between 50 to 2000 ohm- meterMultiple Electrodes
Rocky Soil/ More than 2000 ohm- meterMultiple Electrodes
Transformers, substation earthing, LT line equipment/ 15kAless than 1 ohmNormal Soil/ up to 50 ohm-meterSingle Electrode
Sandy Soil/ between 50 to 2000 ohm- meterMultiple Electrodes
Rocky Soil/ More than 2000 ohm- meterMultiple Electrodes
LA, High current Equipment./ 50kAless than 1 ohmNormal Soil/ up to 50 ohm-meterSingle Electrode
Sandy Soil/ between 50 to 2000 ohm- meterMultiple Electrodes
Rocky Soil/ More than 2000 ohm- meterMultiple Electrodes
PRS, UTS, RTUs, Data processing centre etc./5KAless than 0.5 ohmNormal Soil/ up to 50 ohm-meterSingle Electrode
Sandy Soil/ between 50 to 2000 ohm- meterMultiple Electrodes
Rocky Soil/ More than 2000 ohm- meterMultiple Electrodes
 

Size of Earthing Conductor:

Ref IS 3043 &Handbook on BS 7671: The Lee Wiring Regulations by Trevor E. Marks.
Size of Earthing Conductor
Area of Phase Conductor S (mm2)Area of Earthing conductor (mm2) When It is Same Material as Phase ConductorArea of Earthing conductor (mm2) When It is Not Same Material as Phase Conductor
S < 16 mm2SSX(k1/k2)
16 mm2<S< 35 mm216 mm216X(k1/k2)
S > 35 mm2S/2SX(k1/2k2)
  K1 is the value of Phase conductor,k2 is the value of earthing conductor
Value of K for GI=80, Alu=126,Cu=205 for 1 Sec
 

GI Earthing Strip:

Size (mm2)Weight
20 x 3500 gm Per meter
25 x 3600 gm Per meter
25 x 61/200 Kg Per meter
32 x 61/600 Kg Per meter
40 x 62 Kg Per meter
50 x 62/400 Kg Per meter
65 x 105/200 Kg Per meter
75 x 127/200 Kg Per meter